FullFLOW DX
TCHVTL 1200÷21450
Cooling capacity: 201.7÷1.455.2 kW
WEBCODE: FFD03
Product benefits
- Non-flammable reduced GWP gas
- Various soundproofing options
- Touch interface (optional)
- Free-Cooling management
- Integrated MASTER/SLAVE control


Water-cooled water chillers. Range with stepless semi-hermetic screw compressors and R513A ecological refrigerant gas.
Construction features
• Compressor: high energy efficiency semi-hermetic screw compressor with control of linear capacity, with star-delta or part-winding start up (depending on models) and complete with integral protection, casing heater and refrigerant gas outlet piping shut-off valve.
• Water side heat exchanger (evaporator): dry expansion shell and tube exchanger with counterflow heat exchange, complete with closed cell polyurethane foam rubber insulation, water flow differential pressure switch and Victaulic fittings. Antifreeze heater sizes 1200-1230.
• Water side heat exchanger (condenser): tube and shell complete with differential pressure switch, safety valve, service valve on the high-pressure refrigerant gas circuit.
• Control: microprocessor electronic control.
• Structure: made of galvanised and painted steel plate with polyester powder coating.
• The unit is also complete with:
- clock board;
- display of cooling circuit high/low pressure;
- electronic expansion valve;
- Master/Slave control up to 4 units in parallel;
- 0-10V analogue signal for condensing control from external device;
- control of Variable Primary Flow (VPF_R).
Versions
• T - High efficiency version
Models
• TCHVTL: unit designed for cooling only.
Factory fitted accessories
• 100% heat recovery unit.
• Free-Cooling Management.
• Dry-Cooler Management.
• Set up for heat pump operation.
• Condenser Victaulic fittings.
• Power factor correction capacitors (cosφ > 0.94).
• Circuit breaker switches.
• Forced limit of power consumption.
• Soft starter.
• Inlet compressor shut-off valves.
• Energy parameter measuring device.
• Electro-mechanical flow switch.
• Digital input for double set-point.
• Compressor soundproof enclosures.
• Refrigerant leak detector.
• Full acoustic casing.
• Compressor oil level sensor.
• Double safety valves.
• Control of min/max power supply voltage.
• 4-20 mA analogue signal for shifting set-point.
• Evaporator antifreeze heater (sizes 1290-21450).
• Interfaces for serial communication with other devices.
• Colour touch user keypad (fitted on the machine or remotely) with 7'' display.
• Anti-vibration mountings supplied loose.
• Protective packaging
Separately supplied accessories
• Remote keypad with display.
• Outdoor air temperature probe for set-point compensation
• Thermostat with display.
• Rhoss supervisors for unit monitoring and remote management.
• Rhoss sequencer for integrated management of multiple chillers.
TCHVTL MODEL | ||
❶ | Nominal cooling capacity | kW |
❶ | E.E.R. | |
❶ | Absorbed power | kW |
❷ | Sound power | dB(A) |
Screw/step compressor | no. | |
Circuits | no. | |
Electrical supply | V-ph-Hz | |
DIMENSIONS AND WEIGHT | ||
L - Width | mm | |
H - Height | mm | |
P - Depth | mm | |
❸ | TCHVTL weight | kg |
SEASONAL ENERGY PERFORMANCE | ||
TCHVTL MODEL SEASONAL PERFORMANCE IN COOLING MODE | ||
① | Pdesignc (EN 14825) | kW |
① | SEER (EN 14825) | |
② | ηs,c | % |
1200 | 1230 | 1290 | 1320 | 1380 | 2430 | 2490 | 2540 | 2620 | 2690 | 2770 | 2860 | 2950 | 21030 | 21100 | 21180 | 21250 | 21310 | 21390 | 21450 |
201,7 | 229,7 | 289,7 | 315,6 | 374,5 | 433,6 | 487,5 | 543,5 | 618,4 | 691,4 | 774,4 | 859,4 | 950,4 | 1025,4 | 1098,3 | 1173,2 | 1250,2 | 1310,3 | 1391,2 | 1455,2 |
4,66 | 4,65 | 4,73 | 4,65 | 4,74 | 4,9 | 4,77 | 4,8 | 4,77 | 4,81 | 4,9 | 4,9 | 4,92 | 4,9 | 4,86 | 4,86 | 4,87 | 4,85 | 4,85 | 4,83 |
43,3 | 49,4 | 61,2 | 67,9 | 79 | 88,5 | 102,2 | 113,2 | 129,6 | 143,7 | 158 | 175,4 | 193,2 | 209,3 | 226 | 241,4 | 256,7 | 270,2 | 286,8 | 301,3 |
94 | 94 | 96 | 96 | 96 | 97 | 97 | 97 | 97 | 97 | 98 | 98 | 99 | 99 | 99 | 99 | 99 | 99 | 100 | 100 |
1/ CONTINUOUS LINEAR REGULATION (50-100%) | 2/ CONTINUOUS LINEAR REGULATION (25-100%) | ||||||||||||||||||
1 | 1 | 1 | 1 | 1 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 |
400-3-50 | |||||||||||||||||||
1200 | 1230 | 1290 | 1320 | 1380 | 2430 | 2490 | 2540 | 2620 | 2690 | 2770 | 2860 | 2950 | 21030 | 21100 | 21180 | 21250 | 21310 | 21390 | 21450 |
2860 | 2860 | 3460 | 3460 | 3460 | 4060 | 4060 | 4060 | 4210 | 4240 | 4670 | 4710 | 4850 | 4850 | 4850 | 4850 | 5150 | 5160 | 5130 | 5140 |
1670 | 1670 | 1670 | 1670 | 1670 | 1850 | 1850 | 1850 | 1900 | 1900 | 1980 | 1980 | 2130 | 2130 | 2230 | 2230 | 2230 | 2250 | 2350 | 2350 |
1000 | 1000 | 1000 | 1000 | 1000 | 1320 | 1320 | 1320 | 1320 | 1320 | 1320 | 1320 | 1320 | 1320 | 1320 | 1320 | 1320 | 1320 | 1320 | 1320 |
1300 | 1320 | 1720 | 1730 | 1740 | 2400 | 2400 | 2750 | 3140 | 3260 | 3510 | 3630 | 4640 | 4680 | 4830 | 4940 | 5030 | 5220 | 5590 | 5820 |
1200 | 1230 | 1290 | 1320 | 1380 | 2430 | 2490 | 2540 | 2620 | 2690 | 2770 | 2860 | 2950 | 21030 | 21100 | 21180 | 21250 | 21310 | 21390 | 21450 |
201,7 | 229,7 | 289,7 | 315,6 | 374,5 | 433,6 | 487,5 | 543,5 | 618,4 | 691,4 | 774,4 | 859,4 | 950,4 | 1.025,4 | 1.098,3 | 1.173,2 | 1.250,2 | 1.310,3 | 1.391,2 | 1.455,2 |
5,82 | 5,82 | 5,62 | 5,73 | 5,82 | 6,58 | 6,46 | 6,43 | 6,39 | 6,39 | 6,54 | 6,45 | 6,39 | 6,38 | 6,38 | 6,41 | 6,41 | 6,43 | 6,39 | 6,38 |
230 | 230 | 222 | 226 | 230 | 260 | 255 | 254 | 253 | 252 | 259 | 255 | 253 | 252 | 252 | 253 | 253 | 254 | 253 | 252 |
Data at the following conditions: |
|
❶ |
Chilled water: 7/12°C. - Condenser inlet water: 30/35°C. |
❷ |
Total sound power level in dB(A) based on measurements carried out in accordance with regulation UNI EN-ISO 9614. |
❸ |
Empty weight. |
Performance according to EN 14511. |
|
① |
Low temperature application (7°C) |
② |
Seasonal energy efficiency: low temperature cooling (EU Regulation 2016/2281) |