WinPOWER EXP
TXAEY 4400÷6660EXPsystems - Air cooled multi-purpose ecological system with axial fans. Range with scroll hermetic compressors and R410A refrigerant gas.
Key features
Multi-purpose units with TER up to 8.19
Extended operating limits
Description
Construction features
• Compressor: scroll type, rotary, hermetic complete with thermal protection and casing heater.
• Up to 6 capacity steps with high efficiency at partial loads.
• Main and secondary heat exchangers: crossed flow stainless steel plate exchangers, complete with antifreeze heater, closed cell polyurethane foam rubber insulation and water flow differential pressure switch.
• Air side heat exchanger: finned coil with copper pipes and aluminium fins.
• Fan: external rotor axial type electric fans, equipped with internal thermal protection, accident protection grilles and a proportional electronic device for continuous fan rotation speed regulation (T version; fans with an EC motor are standard in the Q version)
• Control: microprocessor electronic control with Adaptive Function Plus logic.
• Structure: load-bearing structure made of galvanised and painted steel plate with polyester powder coating.
• The unit is also complete with:
- fan and compressor thermal magnetic circuit breakers, heat exchanger antifreeze heater;
- display of cooling circuit high and low pressure;
- electronic expansion valve;
- clock board;
- Master/Slave control up to 4 units in parallel;
- control of Variable Primary Flow (VPF_R).
Versions
• T - High efficiency version.
• Q - Super silenced version complete with compressor technical compartment soundproofing, fans with EC motor at reduced speed.
Models
• TXAETY: EXPsystems unit.
• TXAEQY: super silenced EXPsystems unit.
Factory fitted accessories
• Tube and shell main and secondary heat exchangers.
• PUMP with single or double electric pump, one of which automatic in standby. The electric pumps are available in the main and secondary/recovery heat exchanger low or high head set-ups.
• TANK&PUMP with 700-1000 litre integrated buffer tank (depending on models) and single or double electric pump, complete with expansion tank, air vent valves, safety valve and water side pressure gauge.
• Inverter pump control for unit start-up (TXAEQY).
• Recovery side VPF_R control.
• Desuperheater.
• Condensing control with fans with EC motor (standard in Q versions).
• Condensing control with over-pressure fans (T version only).
• Power factor correction capacitors (cosφ > 0.94).
• Forced limit of power consumption.
• Forced noise limit.
• Energy parameter measuring device.
• Soft starter.
• Compressor box and soundproofed cooling circuit.
• Compressor soundproof enclosures.
• Cooling circuit outlet and inlet valves.
• Refrigerant leak detector.
• Cooling circuit high and low pressure gauges.
• Double safety valves.
• Coil protection nets or metal filters.
• Bottom compartment protection nets.
• Pre-painted copper/aluminium or copper/copper coils.
• Digital input for double set-point.
• 4-20 mA analogue signal for shifting set-point.
• Electrical panel antifreeze heater, buffer tank, electric pumps and desuperheater, if applicable.
• Interfaces for serial communication with other devices.
• Spring anti-vibration mounts.
Separately supplied accessories
• Remote keypad with display.
• Thermostat with display.
• Rhoss supervisors for unit monitoring and remote management.
• Rhoss sequencer for integrated management of multiple chillers.
Technical data
TXAETY MODEL | 4400 | 4440 | 6520 | 6580 | 6660 | ||||
COOLING OPERATIONS (AUTOMATIC 1 MODE) | |||||||||
❶ | Nominal cooling capacity | kW | 397 | 434,8 | 525,4 | 577,4 | 648,1 | ||
❶ | Absorbed power | kW | 131,9 | 145 | 176,4 | 198,5 | 218,3 | ||
❶ | E.E.R. | 3,01 | 3 | 2,98 | 2,91 | 2,97 | |||
COOLING OPERATIONS + TOTAL RECOVERY (AUTOMATIC 2 MODE) | |||||||||
❸ | Nominal cooling capacity | kW | 409,2 | 446,4 | 533,5 | 586,9 | 657,4 | ||
❸ | Recovery heating capacity | kW | 520,2 | 571,4 | 688,1 | 762,6 | 848,6 | ||
❸ | T.E.R. | 8,19 | 7,98 | 7,75 | 7,52 | 7,72 | |||
HEATING OPERATIONS (MODE SELECT 1-2 AUTOMATIC 3) | |||||||||
❷ | Nominal heating capacity | kW | 426,1 | 470,4 | 569,8 | 629,9 | 706,2 | ||
❷ | Absorbed power | kW | 131,2 | 144,3 | 177 | 195,1 | 217,3 | ||
❷ | C.O.P. | 3,25 | 3,26 | 3,22 | 3,23 | 3,25 | |||
TXAEQY MODEL | 4400 | 4440 | 6520 | 6580 | 6660 | ||||
COOLING OPERATIONS (AUTOMATIC 1 MODE) | |||||||||
❶ | Nominal cooling capacity | kW | 379,1 | 408,9 | 497,6 | 540,7 | 609,4 | ||
❶ | Absorbed power | kW | 136,4 | 150,9 | 182,9 | 213,7 | 224,9 | ||
❶ | E.E.R. | 2,78 | 2,71 | 2,72 | 2,53 | 2,71 | |||
COOLING OPERATIONS + TOTAL RECOVERY (AUTOMATIC 2 MODE) | |||||||||
❸ | Nominal cooling capacity | kW | 405,8 | 451,6 | 535 | 589,1 | 659,9 | ||
❸ | Recovery heating capacity | kW | 519,1 | 574,7 | 689,4 | 764,4 | 850,7 | ||
❸ | T.E.R. | 7,99 | 8,16 | 7,76 | 7,55 | 7,75 | |||
HEATING OPERATIONS (MODE SELECT 1-2 AUTOMATIC 3) | |||||||||
❷ | Nominal heating capacity | kW | 420,9 | 462,7 | 569,1 | 622,1 | 696,2 | ||
❷ | Absorbed power | kW | 126,8 | 138,9 | 170,9 | 186,8 | 208,4 | ||
❷ | C.O.P. | 3,32 | 3,33 | 3,33 | 3,33 | 3,34 | |||
TXAETY -TXAEQY MODEL | 4400 | 4440 | 6520 | 6580 | 6660 | ||||
❹ | TXAETY sound pressure | dB(A) | 76 | 76,5 | 76,5 | 76,5 | 76,5 | ||
❹ | TXAEQY sound pressure | dB(A) | 54,5 | 55,5 | 55,5 | 55,5 | 57,5 | ||
❺ | TXAETY sound power | dB(A) | 96 | 97 | 97 | 97 | 98 | ||
❺ | TXAEQY sound power | dB(A) | 87 | 88 | 88 | 88 | 90 | ||
Scroll compressors/steps | n. | 4/4 | 4/4 | 6/6 | 6/6 | 6/6 | |||
Circuits | n. | 2 | 2 | 2 | 2 | 2 | |||
Electrical supply | V-ph-Hz | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | |||
DIMENSIONS AND WEIGHTS | 4400 | 4440 | 6520 | 6580 | 6660 | ||||
L – Width | mm | 4840 | 4840 | 5940 | 5940 | 6840 | |||
H – Height | mm | 2450 | 2450 | 2450 | 2450 | 2450 | |||
P – Depth | mm | 2260 | 2260 | 2260 | 2260 | 2260 | |||
❻ | TXAETY weight | kg | 3650 | 3760 | 4480 | 4580 | 5250 | ||
❻ | TXAEQY weight | kg | 4340 | 4360 | 5270 | 5370 | 6070 | ||
SEASONAL ENERGY PERFORMANCE | 4400 | 4440 | 6520 | 6580 | 6660 | ||||
TXAETY MODEL SEASONAL PERFORMANCE IN COOLING MODE | |||||||||
① | Pdesignc (EN 14825) | kW | - | 434,8 | 525,4 | 577,4 | 648,1 | ||
① | SEER (EN 14825) | - | 4,63 | 4,64 | 4,61 | 4,63 | |||
② | ηs,c | % | - | 182 | 183 | 182 | 182 | ||
TXAEQY MODEL SEASONAL PERFORMANCE IN COOLING MODE | |||||||||
① | Pdesignc (EN 14825) | kW | - | - | 497,6 | 540,7 | 609,4 | ||
① | SEER (EN 14825) | - | - | 4,76 | 4,79 | 4,77 | |||
② | ηs,c | % | - | - | 188 | 189 | 188 | ||
TXAETY MODEL SEASONAL PERFORMANCE IN HEATING MODE | |||||||||
③ | Pdesignh (EN 14825) | kW | 361 | - | - | - | - | ||
③ | SCOP (EN 14825) | 3,63 | - | - | - | - | |||
④ | ηs | % | 142 | - | - | - | - | ||
TXAEQY MODEL SEASONAL PERFORMANCE IN HEATING MODE | |||||||||
③ | Pdesignh (EN 14825) | kW | 358 | 397 | - | - | - | ||
③ | SCOP (EN 14825) | 3,73 | 3,74 | - | - | - | |||
④ | ηs | % | 146 | 147 | - | - | - | ||
- Data at the following conditions:
- ❶ Air: 35°C – Water: 12/7°C.
- ❷ Air: 7°C D.B. – 6°C W.B. – Water: 40/45°C.
- ❸ Evaporator output water: 7℃, nominal flow rate. Recovery output water: 45°C, nominal flow rate.
- ❹ In open field (Q = 2) at 10 m from the unit.
- ❺ Total sound power level in dB(A) based on measurements carried out in accordance with regulation UNI EN-ISO 9614.
- ❻ Weight refers to the unit without load.
- Performance according to EN 14511.
- T.E.R.: Total efficiency ratio
- ① Low temperature application (7°C)
- ② Seasonal energy efficiency: low temperature cooling (EU Regulation 2016/2281)
- ③ In Average climatic conditions, low temperature application (35°C)
- ④ Seasonal energy efficiency: low temperature heating in Average climate (EU Regulations No.811/2013 and No.813/2013)
Manuals
To view all the documents, log in to the reserved area
Technical notes
To view all the documents, log in to the reserved area
Documents
To view all the documents, log in to the reserved area
Images