UniPACK-PI
TCAIP-THAIP 175÷3150Water chillers and packaged reversible air-cooled heat pumps with axial fans. Range with hermetic scroll compressors, DC Inverter and R290 refrigerant.
Key features
Efficient and eco-friendly range in R290
Inverter technology
Full optional unit
Integrated MASTER/SLAVE control
Hot water production from -20°C to 40°C outdoor air
Temperature of the produced water up to 78°C
Description
Construction features
• Compressor: hermetic rotary, scroll type and with Inverter actuation (i, 1+i, 2+i) complete with thermal protection and casing heater.
• Continuous regulation with high efficiency at partial loads.
• Water side heat exchanger: with stainless steel plates, complete with closed cell polyurethane foam rubber insulation and water flow differential pressure switch.
• Air side heat exchanger: featuring micro-channels (TCAIP) or finned coil with copper pipes and aluminium fins (THAIP).
• Fan: external rotor axial type electric fans equipped with internal thermal protection, accident protection grilles and proportional electronic device for continuous fan rotation speed regulation.
• Control: microprocessor electronic control with Adaptive Function Plus logic.
• Structure: load-bearing structure made of galvanised and painted steel plate with polyester powder coating.
• Refrigerant leak detector.
• Coil protection nets.
• The unit is also complete with:
- compressor and fan circuit breaker switches;
- electronic expansion valve;
- display of cooling circuit high and low pressure;
- Master/Slave control up to 4 units in parallel;
- clock board;
- control of Variable Primary Flow (VPF_R);
- automatic management of anti-legionella cycles.
Versions
• T - High efficiency version with oversized condensing section (TCAITP-THAITP).
• Q - Super-silenced version complete with compressor technical compartment soundproofing, reduced speed fans and oversized condensing section (THAITP-THAIQP).
Models
• TCAITP: high efficiency unit designed for cooling only.
• TCAIQP: super silenced unit designed for cooling only.
• THAITP: high efficiency heat pump unit.
• THAIQP: super silenced heat pump unit.
Factory fitted accessories
• PUMP with single or double electric pump, one of which automatic in standby. The electric pumps are available in the low or high head versions.
• TANK&PUMP with 250 - 380 litre integrated buffer tank (depending on the sizes) and single or double electric pump, complete with expansion tank, air vent valves, safety valve and water side pressure gauge.
• Inverter pump control for unit start-up.
• Desuperheater.
• 100% heat recovery unit (TCAIP)
• Condensing control with fans with EC motor.
• Condensing control with over-pressure fans (T version only)
• Power factor correction capacitors (cosφ > 0.94).
• Forced limit of power consumption.
• Forced noise limit.
• Energy parameter measuring device.
• Soft starter.
• Technical compressor compartment soundproofing.
• Compressor soundproof enclosures.
• Double safety valves.
• Buffer panels.
• Microchannel coils with E-coating treatment, copper/copper, copper/aluminium, pre-painted copper/aluminium or with hydrophilic treatment depending on versions.
• Control of min/max power supply voltage and backup battery
• Digital input for double set-point.
• 4-20 mA analogue signal for shifting set-point.
• Contacts for Smart Grid integration and photovoltaic system.
• Evaporator antifreeze heater, electrical panel, buffer tank, electric pumps and heat exchangers for heat recovery, if applicable, and base.
• Low temperature water production.
• Interfaces for serial communication with other devices.
• Colour touch user keypad (fitted on the machine or remotely) with 7'' display.
• Anti-vibration mounts.
Separately supplied accessories
• Remote keypad with display.
• Thermostat with display.
• Rhoss supervisors for unit monitoring and remote management.
• Rhoss sequencer for integrated management of multiple chillers.
Technical data
TCAITP-TCAIQP MODEL | 175 | 290 | 2100 | 3110 | 3120 | 3130 | 3140 | 3150 | ||||
❶ | Nominal cooling capacity | kW | 74,9 | 89,9 | 99,9 | 109,9 | 119,9 | 129,9 | 140,9 | 153,9 | ||
❶ | Nominal cooling capacity | kW | 68,9 | 82,9 | 91,9 | 100,9 | 108,9 | 119,9 | 129,9 | 140,9 | ||
❶ | E.E.R. | 3,07 | 3,36 | 3,22 | 3,16 | 3,15 | 3,29 | 3,24 | 3,21 | |||
❶ | E.E.R. | 3,08 | 3,4 | 3,3 | 3,04 | 3,05 | 3,28 | 3,18 | 3,15 | |||
❶ | Absorbed power | kW | 24,4 | 26,8 | 31 | 34,8 | 38,1 | 39,5 | 43,5 | 47,9 | ||
❶ | Absorbed power | kW | 22,4 | 24,4 | 27,8 | 33,2 | 35,7 | 36,6 | 40,8 | 44,7 | ||
THAITP-THAIQP MODEL | 175 | 290 | 2100 | 3110 | 3120 | 3130 | 3140 | 3150 | ||||
❷ | Nominal heating capacity | kW | 79,1 | 90,1 | 101,1 | 110,1 | 122,1 | 132,1 | 144,1 | 159,2 | ||
❷ | Nominal heating capacity | kW | 72,1 | 83,1 | 92,1 | 105,1 | 115,1 | 121,1 | 133,1 | 145,1 | ||
❷ | C.O.P. | 3,25 | 3,26 | 3,21 | 3,23 | 3,21 | 3,29 | 3,25 | 3,24 | |||
❷ | C.O.P. | 3,29 | 3,36 | 3,31 | 3,36 | 3,35 | 3,34 | 3,3 | 3,28 | |||
❶ | Nominal cooling capacity | kW | 71,9 | 84,9 | 95,9 | 104,9 | 113,9 | 123,9 | 133,9 | 146,9 | ||
❶ | Nominal cooling capacity | kW | 66,9 | 78,9 | 87,9 | 96,9 | 103,9 | 114,9 | 123,9 | 134,9 | ||
❷ | Absorbed power | kW | 24,3 | 27,6 | 31,5 | 34,1 | 38 | 40,2 | 44,3 | 49,1 | ||
❷ | Absorbed power | kW | 21,9 | 24,7 | 27,8 | 31,3 | 34,4 | 36,3 | 40,3 | 44,2 | ||
TCAIP-THAIP MODEL | 175 | 290 | 2100 | 3110 | 3120 | 3130 | 3140 | 3150 | ||||
❸ | TCAITP-THAITP sound pressure | dB(A) | 55 | 54 | 55 | 55 | 55 | 55 | 56 | 57 | ||
❸ | TCAIQP-THAIQP sound pressure | dB(A) | 50 | 49 | 50 | 50 | 50 | 50 | 51 | 52 | ||
❹ | TCAITP-THAITP sound power | dB(A) | 87 | 86 | 87 | 87 | 87 | 87 | 88 | 89 | ||
❹ | TCAIQP-THAIQP sound power | dB(A) | 82 | 81 | 82 | 82 | 82 | 82 | 83 | 84 | ||
Scroll compressors/steps | n. | 1 inverter | 1 inverter + 1 | 1 inverter + 1 | 1 inverter + 2 | 1 inverter + 2 | 1 inverter + 2 | 1 inverter + 2 | 1 inverter + 2 | |||
Circuits | n. | 1 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | |||
Electrical supply | V-ph-Hz | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | |||
DIMENSIONS AND WEIGHTS | 175 | 290 | 2100 | 3110 | 3120 | 3130 | 3140 | 3150 | ||||
L – Width | mm | 3250 | 3250 | 3250 | 3250 | 3250 | 3930 | 3930 | 3930 | |||
H – Height | mm | 2260 | 2260 | 2260 | 2260 | 2260 | 2260 | 2260 | 2260 | |||
P – Depth | mm | 1270 | 1970 | 1970 | 1970 | 1970 | 1970 | 1970 | 1970 | |||
❺ | TCAITP weight | kg | 1025 | 1495 | 1510 | 1595 | 1620 | 1835 | 1860 | 1865 | ||
❺ | THAITP weight | kg | 1215 | 1695 | 1730 | 1815 | 1860 | 2105 | 2130 | 2135 | ||
SEASONAL ENERGY PERFORMANCE | 175 | 290 | 2100 | 3110 | 3120 | 3130 | 3140 | 3150 | ||||
TCAITP MODEL SEASONAL PERFORMANCE IN COOLING MODE | ||||||||||||
① | Pdesignc (EN 14825) | kW | 74,9 | 89,9 | 99,9 | 109,9 | 119,9 | 129,9 | 140,9 | 153,9 | ||
① | SEER (EN 14825) | 5,14 | 4,81 | 4,75 | 4,53 | 4,62 | 4,67 | 4,63 | 4,76 | |||
② | ηs,c | % | 202 | 189 | 187 | 178 | 182 | 184 | 182 | 187 | ||
TCAIQP MODEL SEASONAL PERFORMANCE IN COOLING MODE | ||||||||||||
① | Pdesignc (EN 14825) | kW | 68,9 | 82,9 | 91,9 | 100,9 | 108,9 | 119,9 | 129,9 | 140,9 | ||
① | SEER (EN 14825) | 5,17 | 4,83 | 4,79 | 4,6 | 4,67 | 4,72 | 4,68 | 4,81 | |||
② | ηs,c | % | 204 | 190 | 188 | 181 | 184 | 186 | 184 | 189 | ||
THAITP MODEL SEASONAL PERFORMANCE IN HEATING MODE – Low temperature application 35°C | ||||||||||||
③ | Pdesignh (EN 14825) | kW | 65 | 74 | 83 | 90 | 100 | 108 | 118 | 130 | ||
③ | SCOP (EN 14825) | 4,31 | 3,9 | 3,91 | 4,11 | 4,13 | 4,07 | 4,11 | 4,14 | |||
④ | ηs | % | 170 | 153 | 154 | 162 | 162 | 160 | 161 | 163 | ||
④ | Energy class | A++ | - | - | - | - | - | - | - | |||
THAIQP MODEL SEASONAL PERFORMANCE IN HEATING MODE – Low temperature application 35°C | ||||||||||||
③ | Pdesignh (EN 14825) | kW | 59 | 68 | 75 | 86 | 94 | 99 | 109 | 119 | ||
③ | SCOP (EN 14825) | 4,37 | 3,91 | 3,94 | 4,15 | 4,17 | 4,13 | 4,15 | 4,2 | |||
④ | ηs | % | 172 | 153 | 155 | 163 | 164 | 162 | 163 | 165 | ||
④ | Energy class | A++ | A++ | - | - | - | - | - | - | |||
THAITP MODEL SEASONAL PERFORMANCE IN HEATING MODE – Medium temperature application 55°C | ||||||||||||
③ | Pdesignh (EN 14825) | kW | 62 | 72 | 81 | 88 | 98 | 105 | 116 | 128 | ||
③ | SCOP (EN 14825) | 3,57 | 3,25 | 3,25 | 3,37 | 3,38 | 3,42 | 3,38 | 3,45 | |||
④ | ηs | % | 140 | 127 | 127 | 132 | 132 | 134 | 132 | 135 | ||
④ | Energy class | A++ | - | - | - | - | - | - | - | |||
THAIQP MODEL SEASONAL PERFORMANCE IN HEATING MODE – Medium temperature application 55°C | ||||||||||||
③ | Pdesignh (EN 14825) | kW | 56 | 66 | 74 | 84 | 93 | 97 | 107 | 117 | ||
③ | SCOP (EN 14825) | 3,56 | 3,22 | 3,23 | 3,4 | 3,39 | 3,36 | 3,39 | 3,38 | |||
④ | ηs | % | 139 | 126 | 126 | 133 | 133 | 131 | 133 | 132 | ||
④ | Energy class | A++ | A++ | - | - | - | - | - | - | |||
- Data at the following conditions:
- ❶ Air: 35°C – Water: 12/7°C
- ❷ Air: 7°C, D.B. – 6°C W.B.- Water: 40/45°C.
- ❸ In open field (Q = 2) at 10 m from the unit.
- ❹ Total sound power level in dB(A) based on measurements carried out in accordance with regulation UNI EN-ISO 9614.
- ❺ Weight referred to the unit without load and not accessorised.
- ■ TCAIQP-THAIQP super-silenced versions.
- Performance according to EN 14511.
- ① Low temperature application (7°C)
- ② Seasonal energy efficiency: low temperature cooling (EU Regulation 2016/2281)
- ③ In Average climatic conditions
- ④ Seasonal energy efficiency: low temperature heating in Average climate (EU Regulations No.811/2013 and No.813/2013 – class between D and A+++)
Manuals
To view all the documents, log in to the reserved area
Technical notes
To view all the documents, log in to the reserved area
Documents
To view all the documents, log in to the reserved area
Images

Request information about this product
Find a reseller in your area for a customized offer on Rhoss air conditioning solutions.