FullFLOW ECO DX FullFLOW ECOA1 DX
TCHVT 1230÷21530 / TOHVT 1230÷21200-
TCHVT 2560
Water chillers and packaged non-reversible heat pumps with water source .Range with semi-hermetic screw compressors and R1234ze or R515B refrigerant gas.
Key features
Efficient and eco-friendly range in R1234ze or R515B
Various soundproofing options
Touch interface (optional)
Free-Cooling management
Integrated MASTER/SLAVE control
Description
Construction features
• Compressor: high energy efficiency semi-hermetic screw compressor with control of linear capacity, with star-delta or part-winding start up (depending on models) and complete with integral protection, casing heater and refrigerant gas outlet piping shut-off valve.
• Water side heat exchanger (evaporator): dry expansion shell and tube exchanger with counterflow heat exchange, complete with closed cell polyurethane foam rubber insulation, water flow differential pressure switch and Victaulic fittings.
• Water side heat exchanger (condenser): tube and shell complete with water flow differential pressure switch (TOHVT), safety valve, service valve on the high-pressure refrigerant gas circuit.
• Control: microprocessor electronic control.
• Structure: made of galvanised and painted steel plate with polyester powder coating.
• The unit is also complete with:
- clock board;
- display of cooling circuit high/low pressure;
- electronic expansion valve;
- Master/Slave control up to 4 units in parallel;
- 0-10V analogue signal for condensing control/water flow modulation from external device;
- control of Variable Primary Flow (VPF_R), for TCHVT.
Versions
• T - High efficiency version
Models
• TCHVTE: unit designed for cooling only with R1234ze gas.
• TCHVTO: unit designed for cooling only with R515B gas.
• TOHVTE: unit designed for heating only with R1234ze gas.
• TOHVTO: unit designed for heating only with R515B gas.
Factory fitted accessories
• VPF control (TOHVT).
• 100% heat recovery unit (TCHVT).
• Free-Cooling Management (TCHVT).
• Dry-Cooler Management (TCHVT).
• Set up for heat pump operation (TCHVT).
• Set up for operating limits extension (TOHVT).
• Condenser Victaulic fittings.
• Power factor correction capacitors (cosφ > 0.94).
• Circuit breaker switches.
• Forced limit of power consumption.
• Soft starter.
• Inlet compressor shut-off valves.
• Energy parameter measuring device.
• Electro-mechanical flow switch.
• Digital input for double set-point.
• Refrigerant leak detector.
• Soundproofed compressor box.
• Full acoustic casing.
• Compressor oil level sensor.
• Double safety valves.
• Control of min/max power supply voltage.
• Low temperature water production (TCHVT).
• 4-20 mA analogue signal for shifting set-point.
• Contacts for Smart Grid integration and photovoltaic system.
• Evaporator antifreeze heater.
• Interfaces for serial communication with other devices.
• Colour touch user keypad (fitted on the machine or remotely) with 7'' display.
• Anti-vibration mountings supplied loose.
• Protective packaging
Separately supplied accessories
• Remote keypad with display.
• Outdoor air temperature probe for set-point compensation
• Thermostat with display.
• Rhoss supervisors for unit monitoring and remote management.
• Rhoss sequencer for integrated management of multiple chillers.
Technical data
| TCHVTE-TCHVTO MODEL | 1230 | 1280 | 1340 | 1380 | 2450 | 2500 | 2560 | 2620 | 2680 | 2760 | 2830 | 2900 | 2950 | 21000 | 21090 | 21140 | 21200 | 21300 | 21410 | 21530 (*) | ||||
| ❶ | Nominal cooling capacity | kW | 227,8 | 280,5 | 344,9 | 381,2 | 455,9 | 503,8 | 560,5 | 621,2 | 682,9 | 756,7 | 830,2 | 896,6 | 950 | 996,9 | 1088,2 | 1139,9 | 1203,4 | 1303,8 | 1408,2 | 1534,8 | ||
| ❶ | E.E.R. | 4,93 | 4,8 | 4,82 | 4,79 | 4,9 | 4,79 | 4,77 | 4,78 | 4,79 | 4,8 | 5,02 | 5,02 | 5,02 | 4,98 | 4,78 | 4,82 | 4,89 | 4,98 | 5,03 | 5,08 | |||
| ❶ | Absorbed power | kW | 46,2 | 58,4 | 71,6 | 79,6 | 93 | 105,2 | 117,5 | 130 | 142,6 | 157,6 | 165,4 | 178,6 | 189,2 | 200,2 | 227,7 | 236,5 | 246,1 | 261,8 | 280 | 302,1 | ||
| TOHVTE-TOHVTO MODEL | 1230 | 1280 | 1340 | 1380 | 2450 | 2500 | 2560 | 2620 | 2680 | 2760 | 2830 | 2900 | 2950 | 21000 | 21090 | 21140 | 21200 | - | - | - | ||||
| ❷ | Heating capacity | kW | 266,4 | 335 | 390,3 | 442,4 | 530,2 | 595 | 661,8 | 725,1 | 777,2 | 883,9 | 951,1 | 1019,7 | 1085 | 1141,5 | 1237,1 | 1289,3 | 1351,6 | - | - | - | ||
| ❷ | C.O.P. | 4,44 | 4,3 | 4,26 | 4,37 | 4,46 | 4,31 | 4,25 | 4,3 | 4,27 | 4,39 | 4,44 | 4,39 | 4,45 | 4,42 | 4,35 | 4,36 | 4,4 | - | - | - | |||
| ❷ | Absorbed power | kW | 60 | 77,9 | 91,6 | 101,2 | 118,9 | 138,1 | 155,7 | 168,6 | 182 | 201,3 | 214,2 | 232,3 | 243,8 | 258,3 | 284,4 | 295,7 | 307,2 | - | - | - | ||
| TCHVTE-TCHVTO-TOHVTE-TOHVTO MODEL | 1230 | 1280 | 1340 | 1380 | 2450 | 2500 | 2560 | 2620 | 2680 | 2760 | 2830 | 2900 | 2950 | 21000 | 21090 | 21140 | 21200 | 21300 | 21410 | 21530 | ||||
| ❸ | Sound power TCHVTE-TCHVTO | dB(A) | 96 | 96 | 96 | 96 | 97 | 97 | 97 | 98 | 98 | 98 | 99 | 99 | 99 | 99 | 100 | 100 | 100 | 102 | 104 | 104 | ||
| ❸ | Sound power TOHVTE-TOHVTO | dB(A) | 96,5 | 96,5 | 96,5 | 96,5 | 97,5 | 97,5 | 97,5 | 99 | 99 | 99 | 100 | 100,5 | 100,5 | 100,5 | 101,5 | 102 | 102 | - | - | - | ||
| Screw compressors | no. | 1 | 1 | 1 | 1 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | |||
| Circuits | no. | 1 | 1 | 1 | 1 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | |||
| Electrical supply | V-ph-Hz | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | |||
| DIMENSIONS AND WEIGHT | 1230 | 1280 | 1340 | 1380 | 2450 | 2500 | 2560 | 2620 | 2680 | 2760 | 2830 | 2900 | 2950 | 21000 | 21090 | 21140 | 21200 | 21300 | 21410 | 21530 | ||||
| L – Width | mm | 1040 | 1040 | 1040 | 1040 | 1370 | 1370 | 1370 | 1370 | 1370 | 1370 | 1370 | 1370 | 1370 | 1370 | 1370 | 1370 | 1370 | 1470 | 1470 | 1470 | |||
| H – Height | mm | 1780 | 1780 | 1780 | 1780 | 2010 | 2080 | 2080 | 2080 | 2270 | 2270 | 2340 | 2340 | 2340 | 2340 | 2340 | 2340 | 2350 | 2500 | 2500 | 2500 | |||
| P – Depth | mm | 3500 | 3550 | 3550 | 3590 | 4040 | 4050 | 4080 | 4400 | 4750 | 4810 | 4820 | 4820 | 4820 | 4820 | 5140 | 5230 | 5230 | 5350 | 5680 | 5680 | |||
| ❹ | TCHVTE-TCHVTO weight | kg | 1700 | 1720 | 2260 | 2370 | 3050 | 3080 | 3090 | 3720 | 4300 | 4540 | 4780 | 4850 | 4900 | 4920 | 5230 | 5270 | 5320 | 6020 | 6610 | 6980 | ||
| ❹ | TOHVTE-TOHVTO weight | kg | 1715 | 1735 | 2275 | 2385 | 3070 | 3100 | 3110 | 3740 | 4320 | 4560 | 4800 | 4870 | 4920 | 4940 | 5310 | 5370 | 5440 | - | - | - | ||
| SEASONAL ENERGY PERFORMANCE | 1230 | 1280 | 1340 | 1380 | 2450 | 2500 | 2560 | 2620 | 2680 | 2760 | 2830 | 2900 | 2950 | 21000 | 21090 | 21140 | 21200 | 21300 | 21410 | 21530 (*) | ||||
| TCHVTE-TCHVTO MODEL SEASONAL PERFORMANCE IN COOLING MODE | ||||||||||||||||||||||||
| ① | Pdesignc (EN 14825) | kW | 227,8 | 280,5 | 344,9 | 381,2 | 455,9 | 503,8 | 560,5 | 621,2 | 682,9 | 756,7 | 830,2 | 896,6 | 950 | 996,9 | 1088,2 | 1139,9 | 1203,4 | 1303,8 | 1408,2 | 1534,8 | ||
| ① | SEER (EN 14825) | 5,78 | 5,76 | 5,77 | 5,85 | 6,48 | 6,42 | 6,44 | 6,4 | 6,4 | 6,42 | 6,52 | 6,54 | 6,48 | 6,45 | 6,49 | 6,5 | 6,53 | 6,72 | 6,75 | 6,98 | |||
| ② | ηs,c | % | 228 | 227 | 228 | 231 | 256 | 254 | 255 | 253 | 253 | 254 | 258 | 259 | 256 | 255 | 257 | 257 | 258 | 266 | 267 | 276 | ||
| TOHVTE-TOHVTO MODEL SEASONAL PERFORMANCE IN HEATING MODE | ||||||||||||||||||||||||
| ③ | Pdesignh (EN 14825) | kW | 299 | 371 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | ||
| ③ | SCOP (EN 14825) | 4,33 | 4,37 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |||
| ④ | ηs | % | 165 | 167 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | ||
- Data at the following conditions:
- ❶ Chilled water: 12/7 °C – Condenser water: 30/35 °C.
- ❷ Hot water: 40/45 °C – Evaporator water: 10/7 °C.
- ❸ Total sound power level in dB(A) based on measurements carried out in accordance with regulation UNI EN-ISO 9614 (not Eurovent certified).
- ❹ Empty weight.
- Performance according to EN 14511.
- (*) Unit not Eurovent certified.
- ① Low temperature application (7°C)
- ② Seasonal energy efficiency: low temperature cooling (EU Regulation 2016/2281)
- ③ In Average climatic conditions, medium temperature application (55°C)
- ④ Seasonal energy efficiency: medium temperature heating in Average climate (EU Regulations No.811/2013 and No.813/2013)
Manuals
To view all the documents, log in to the reserved area
Technical notes
To view all the documents, log in to the reserved area
Documents
To view all the documents, log in to the reserved area
Images
Request information about this product
Find a reseller in your area for a customized offer on Rhoss air conditioning solutions.