Electa-PI
THAITP 104-116-
Electa-PI THAITP 104÷114 -
Electa-PI THAITP 116
Packaged reversible air-to-water heat pumps with DC inverter compressors and R290 refrigerant gas.
Key features
Efficient and ecological range in R290
Class A+++
Water temperature up to 80°C
Domestic hot water production from –25°C to +45°C outdoor air
Full inverter unit with EC circulator and degasser
Integrated management of the plant and DHW production.
MASTER/SLAVE management of up to 6 units
New total-black design with touch control
APP for managing the unit via smartphone (iOS and Android)
Accessory inertial tank under the unit
Description
Construction features
• Compressor: hermetic, rotary DC Inverter, complete with thermal protection and casing heater.
• Expansion valve: electronic.
• Water side heat exchanger: adequately insulated stainless steel plates, complete with antifreeze heater.
• Air side heat exchanger: finned coil with copper pipes and aluminium-manganese fins with Golden Fin anti-corrosion treatment in epoxy resin and hydrophilic treatment.
• Fan: helical type impeller with EC brushless motor with electronic speed control, equipped with internal thermal protection and accident protection grilles.
• Structure: made of galvanized sheet steel black colour painted (Pantone black C), complete with condensate drain pan and unit base antifreeze heater.
• Control: microprocessor electronic control with remote touch-screen control panel, for integrated management of the heat pump and the heating system, according to the various requirements relating to the use of the energy sources.
- 3-way diverter valve management for production of domestic hot water (DHW).
- Solar thermal management.
- Rapid heating function for domestic hot water.
- Anti-legionella cycle function, with activation timer.
- Auxiliary or supplementary heat source management.
- Secondary circuit management, high and low-temperature with mixing valve.
- On/off valve management for shutting off a part of the system, in heating or cooling mode.
- Management of water or ambient air temperature, using a probe in the control panel or KSOA accessory.
- Management through a room thermostat.
- Master/Slave management of up to 6 units in parallel.
- Operation in silent mode with timer.
- Weekly and daily time slots.
- Holiday mode and antifreeze function.
- Power consumption limiting function.
- Energy consumption trends.
- Parental control and start-up menu password.
- Unit remote on/off and DHW mode activation, from external contact (digital inputs).
- Contacts for Smart Grid and photovoltaic system integration (digital inputs).
- Additional/Secondary/DHW recirculation pump and DHW diverter valve contacts (digital outputs).
- RS485 interface for serial communication with other devices (Modbus RTU protocol).
- iOS and Android APP for managing the unit via smartphone and tablet
• Unit complete with:
- Outdoor temperature probe for set-point compensation.
- Room air temperature probe on the remote control panel.
- Water temperature probe for domestic hot water storage tank (20 m).
- Water temperature probe for auxiliary or supplementary heat source (5,6 m).
- Connection cable for touch-screen (8 m).
Models
• THAITP: heat pump unit.
PUMP set-up
• Pump unit complete with: EC circulator, automatic air vent valve,dearetor with safety valve (2,5 bar), flow switch, expansion tank (5 l), water filter.
Accessories supplied separately
KAI-100 - Inertial storage tank, with function of thermal flywheel or hydraulic separator, for outdoor installation below the Electa-PI unit; 33W leakage losses, energy class A (class between F and A+).
KTAI-100 - Connection pipe between Electa-PI unit and KAI tank.
KSA - Rubber anti-vibration mounts.
KVDEV - 3-way diverter valve for the production of domestic hot water, managed by regulation.
KRIT - Supplementary electric resistance for heat pump, managed by the control system.
KPRU - Touch-screen connection cable (30 m) as an alternative to the cable supplied as standard.
KSOA - Remote air temperature sensor for managing the unit at the room set point (with KCSOA connection cable compulsory).
KCSOA - KSOA room sensor connection cable (10 m).
KWTSM - Mixed water secondary circuit probe (8 m).
KWTSS - Solar thermal probe (20 m).
KPRP - Cabling for RS485 serial connection to the touch screen panel.
KSMS - Serial cable for slave unit connection (8 m), in case of master/slave management.
Technical data
| MODELLO THAITP | 104 M | 106 M | 108 M | 110 M | 112 M | 114 M | 116 M | 116 T | ||||
| ❶ | Heating capacity | kW | 4,5 | 6,1 | 8,2 | 10 | 12 | 14 | 15,5 | 15,5 | ||
| ❶ | Absorbed power | kW | 1,1 | 1,56 | 2,1 | 2,7 | 3,16 | 3,78 | 4,13 | 4,13 | ||
| ❶ | C.O.P. | 4,1 | 3,9 | 3,9 | 3,7 | 3,8 | 3,7 | 3,75 | 3,75 | |||
| ❷ | Heating capacity | kW | 4,5 | 6,2 | 8,4 | 10 | 12 | 14 | 15,5 | 15,5 | ||
| ❷ | Absorbed power | kW | 0,87 | 1,22 | 1,68 | 2,11 | 2,42 | 2,98 | 3,3 | 3,3 | ||
| ❷ | C.O.P. | 5,2 | 5 | 5 | 4,75 | 4,95 | 4,7 | 4,7 | 4,7 | |||
| ❸ | Heating capacity | kW | 4 | 6 | 7,2 | 8,5 | 12 | 14 | 15,5 | 15,5 | ||
| ❸ | Absorbed power | kW | 1,05 | 1,62 | 2 | 2,58 | 3,87 | 4,67 | 5,17 | 5,17 | ||
| ❸ | C.O.P. | 3,8 | 3,7 | 3,6 | 3,3 | 3,1 | 3 | 3 | 3 | |||
| ❹ | Heating capacity | kW | 4 | 5,5 | 7 | 8 | 10 | 11,5 | 12 | 12 | ||
| ❹ | Absorbed power | kW | 1,26 | 1,79 | 2,34 | 2,86 | 3,57 | 4,25 | 4,25 | 4,25 | ||
| ❹ | C.O.P. | 3,19 | 3,07 | 3 | 2,8 | 2,8 | 2,71 | 2,82 | 2,82 | |||
| ❺ | Cooling capacity | kW | 4,5 | 6,1 | 7,5 | 8,9 | 11,6 | 12,8 | 14 | 14 | ||
| ❺ | Absorbed power | kW | 1,2 | 1,91 | 2,34 | 2,92 | 3,68 | 4,34 | 4,91 | 4,91 | ||
| ❺ | E.E.R. | 3,75 | 3,2 | 3,2 | 3,05 | 3,15 | 2,95 | 2,85 | 2,85 | |||
| ❻ | Cooling capacity | kW | 4,5 | 6,2 | 8,3 | 10 | 12 | 14 | 15,5 | 15,5 | ||
| ❻ | Absorbed power | kW | 0,8 | 1,19 | 1,6 | 2,08 | 2,61 | 3,26 | 3,52 | 3,52 | ||
| ❻ | E.E.R. | 5,65 | 5,2 | 5,2 | 4,9 | 4,6 | 4,3 | 4,4 | 4,4 | |||
| ❺ | Available circulator head | kPa | 77 | 68 | 67 | 62 | 58 | 53 | 47 | 47 | ||
| KAI Buffer tank water content | l | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | |||
| ❼ | Sound pressure | dB(A) | 39 | 39 | 42 | 42 | 44 | 44 | 41 | 41 | ||
| ❽ | Sound power | dB(A) | 65 | 65 | 68 | 68 | 70 | 70 | 67 | 67 | ||
| ❾ | Sound power EN12102 | dB(A) | 54 | 54 | 56 | 56 | 58 | 58 | 57 | 57 | ||
| Electrical supply | V-ph-Hz | 230-1-50 | 230-1-50 | 230-1-50 | 230-1-50 | 230-1-50 | 230-1-50 | 230-1-50 | 400-3+N-50 | |||
| DIMENSIONS AND WEIGHTS | 104 M | 106 M | 108 M | 110 M | 112 M | 114 M | 116 M | 116 T | ||||
| L – Width | mm | 1210 | 1210 | 1210 | 1210 | 1210 | 1210 | 940 | 940 | |||
| H – Height | mm | 880 | 880 | 880 | 880 | 880 | 880 | 1615 | 1615 | |||
| P – Depth | mm | 450 | 450 | 450 | 450 | 450 | 450 | 460 | 460 | |||
| ❿ | THAITP Weight | kg | 128 | 128 | 135 | 135 | 155 | 155 | 197 | 197 | ||
| L – Width+KAI | mm | 1210 | 1210 | 1210 | 1210 | 1210 | 1210 | 2245 | 2245 | |||
| H – Height+KAI | mm | 1515 | 1515 | 1515 | 1515 | 1515 | 1515 | 1515 | 1515 | |||
| P – Depth+KAI | mm | 610 | 610 | 610 | 610 | 610 | 610 | 610 | 610 | |||
| ❿ | THAITP Weight+KAI | kg | 198 | 198 | 206 | 206 | 226 | 226 | 267 | 267 | ||
| SEASONAL ENERGY PERFORMANCE | 104 M | 106 M | 108 M | 110 M | 112 M | 114 M | 116 M | 116 T | ||||
| THAITP MODEL SEASONAL PERFORMANCE IN HEATING MODE – Low temperature application 35°C (*) | ||||||||||||
| ③ | Pdesignh (EN 14825) | kW | 5 | 6 | 8 | 9 | 12 | 13 | 14 | 14 | ||
| ③ | SCOP (EN 14825) | 5,13 | 5,18 | 5,13 | 4,93 | 4,75 | 4,73 | 4,75 | 4,7 | |||
| ④ | ηs | % | 202 | 204 | 202 | 194 | 187 | 186 | 187 | 185 | ||
| ④ | Energy class | A+++ | A+++ | A+++ | A+++ | A+++ | A+++ | A+++ | A+++ | |||
| THAITP MODEL SEASONAL PERFORMANCE IN HEATING MODE – Medium temperature application 55°C | ||||||||||||
| ③ | Pdesignh (EN 14825) | kW | 5 | 6 | 7 | 8 | 12 | 13 | 14 | 14 | ||
| ③ | SCOP (EN 14825) | 3,87 | 3,87 | 3,87 | 3,87 | 3,57 | 3,55 | 3,5 | 3,43 | |||
| ④ | ηs | % | 152 | 152 | 152 | 152 | 140 | 139 | 137 | 134 | ||
| ④ | Energy class | A+++ | A+++ | A+++ | A+++ | A++ | A++ | A++ | A++ |
- Data at the following conditions:
- ❶ Air: 7°C D.B. – 6°C W.B. – Water: 40/45°C.
- ❷ Air: 7°C D.B. – 6°C W.B. – Water: 30/35°C.
- ❸ Air: 7°C D.B. – 6°C W.B. – Water: 47/55°C.
- ❹ Air: -7°C D.B. – Water: 30/35°C (not Eurovent certified).
- ❺ Air: 35°C D.B. – Water: 12/7°C.
- ❻ Air: 35°C D.B. – Water: 23/18°C (not Eurovent certified).
- ❼ In open field (Q = 2) at 5 m from the unit.
- ❽ Data according UNI EN-ISO 9614.
- ❾ Data according UNI EN-ISO 9614, EN12102.
- ❿ Weight refers to the empty unit.
- Performance according to EN 14511
- ③ In Average climatic conditions.
- ④ Seasonal energy efficiency: ambient heating in Average climate (EU Regulations No.811/2013 and No.813/2013- class between D and A+++).
- (*) not Eurovent certified.
Manuals
To view all the documents, log in to the reserved area
Technical notes
To view all the documents, log in to the reserved area
Documents
To view all the documents, log in to the reserved area
Request information about this product
Find a reseller in your area for a customized offer on Rhoss air conditioning solutions.
