WinPACK-P EXP
TXAEP 4200÷6430-
TXAETP 4220
EXPsystems – Air cooled multi-purpose system with axial fans.
Range with scroll hermetic compressors and R290 refrigerant gas.
Key features
Efficient range in R290
Temperature of the produced water up to 75°C
TER up to 8,16
Extended operating limits
Integrated MASTER/SLAVE control
Description
Construction features
• Compressor: hermetic rotary, scroll type, complete with thermal protection and casing heater.
• 4÷6 capacity steps with high efficiency at partial loads.
• Water side heat exchanger: with stainless steel plates, complete with closed cell polyurethane foam rubber insulation and water flow differential pressure switch.
• Air side heat exchanger: featuring finned coil with copper pipes and aluminium fins.
• Fan: external rotor axial type electric fans equipped with internal thermal protection, accident protection grilles and proportional electronic device for continuous fan rotation speed regulation.
• Control: microprocessor electronic control with Adaptive Function Plus logic.
• Structure: load-bearing structure made of galvanised and painted steel plate with polyester powder coating.
• Refrigerant leak detector.
• The unit is also complete with:
- compressor and fan circuit breaker switches;
- electronic expansion valve;
- display of cooling circuit high and low pressure;
- Master/Slave control up to 4 units in parallel;
- clock board;
- control of Variable Primary Flow (VPF_R);
- automatic management of anti-legionella cycles.
Versions
• T - High efficiency version.
• Q - Super silenced version complete with compressor technical compartment soundproofing and reduced speed fans.
Models
• TXAETP: EXPsystems unit.
• TXAEQP: super silenced EXPsystems unit.
Factory fitted accessories
• PUMP with single or double electric pump, one of which automatic in standby. The electric pumps are available in the low or high head versions.
• Inverter pump control for unit start-up.
• Recovery side VPF_R control.
• Condensing control with fans with EC motor.
• Condensing control with over-pressure fans (T version only)
• Power factor correction capacitors (cosφ > 0.94).
• Forced limit of power consumption.
• Forced noise limit.
• Energy parameter measuring device.
• Soft starter.
• Compressor technical compartment soundproofing.
• Compressor soundproof enclosures.
• Double safety valves.
• Buffer panels.
• Copper/copper, pre-painted copper/aluminium or with hydrophilic treatment coils.
• Control of min/max power supply voltage.
• Digital input for double set-point.
• 4-20 mA analogue signal for shifting set-point.
• Contacts for Smart Grid integration and photovoltaic system.
• Electrical panel resistance, base, electric pumps and heat exchangers for heat recovery, if any.
• Interfaces for serial communication with other devices.
• Colour touch user keypad (fitted on the machine or remotely) with 7” display.
• Anti-vibration mounts.
Separately supplied accessories
• Remote keypad with display.
• Thermostat with display.
• Rhoss supervisors for unit monitoring and remote management.
• Rhoss sequencer for integrated management of multiple chillers.
Technical data
| TXAETP MODEL | 4200 | 4220 | 4250 | 4270 | 4290 | 5320 | 5360 | 6380 | 6430 | ||||
| COOLING OPERATIONS (AUTOMATIC 1 MODE) | |||||||||||||
| ❶ | Nominal cooling capacity | kW | 192,7 | 212,7 | 240,7 | 260,7 | 281,7 | 309,7 | 347,7 | 372,7 | 414,7 | ||
| ❶ | Absorbed power | kW | 64,4 | 72,3 | 79,2 | 86,3 | 93,9 | 101,5 | 117,1 | 125,5 | 141,5 | ||
| ❶ | E.E.R. | 2,99 | 2,94 | 3,04 | 3,02 | 3 | 3,05 | 2,97 | 2,97 | 2,93 | |||
| COOLING OPERATIONS + TOTAL RECOVERY (AUTOMATIC 2 MODE) | |||||||||||||
| ❸ | Nominal cooling capacity | kW | 195,7 | 220,3 | 241,7 | 264,2 | 289,1 | 308,6 | 351,9 | 380,4 | 424,7 | ||
| ❸ | Recovery heating capacity | kW | 248,9 | 279,4 | 307,9 | 336,2 | 367,6 | 396 | 451,4 | 485,6 | 542,9 | ||
| ❸ | T.E.R. | 8,04 | 8,14 | 7,97 | 8 | 8,02 | 7,75 | 7,77 | 7,93 | 7,88 | |||
| HEATING OPERATIONS (MODE SELECT 1-2 AUTOMATIC 3) | |||||||||||||
| ❷ | Nominal heating capacity | kW | 199,3 | 217,3 | 253,3 | 273,3 | 293,3 | 328,3 | 367,3 | 392,3 | 430,3 | ||
| ❷ | Absorbed power | kW | 61,5 | 67,5 | 77,5 | 83,6 | 89,7 | 100,4 | 113 | 120,7 | 132,8 | ||
| ❷ | C.O.P. | 3,24 | 3,22 | 3,27 | 3,27 | 3,27 | 3,27 | 3,25 | 3,25 | 3,24 | |||
| TXAEQP MODEL | 4200 | 4220 | 4250 | 4270 | 4290 | 5320 | 5360 | 6380 | 6430 | ||||
| COOLING OPERATIONS (AUTOMATIC 1 MODE) | |||||||||||||
| ❶ | Nominal cooling capacity | kW | 187,8 | 206,8 | 235,6 | 254,7 | 274,7 | 303,6 | 339,6 | 362,6 | 403,7 | ||
| ❶ | Absorbed power | kW | 65,9 | 74,1 | 79,9 | 87,5 | 95,4 | 102,2 | 118,3 | 127,2 | 144,7 | ||
| ❶ | E.E.R. | 2,85 | 2,79 | 2,95 | 2,91 | 2,88 | 2,97 | 2,87 | 2,85 | 2,79 | |||
| COOLING OPERATIONS + TOTAL RECOVERY (AUTOMATIC 2 MODE) | |||||||||||||
| ❸ | Nominal cooling capacity | kW | 196 | 220,7 | 242,1 | 264,7 | 289,7 | 309 | 352,4 | 381 | 425,4 | ||
| ❸ | Recovery heating capacity | kW | 249,2 | 279,9 | 308,2 | 336,6 | 368,2 | 396,4 | 452 | 486,2 | 543,6 | ||
| ❸ | T.E.R. | 8,07 | 8,16 | 7,99 | 8,02 | 8,05 | 7,77 | 7,78 | 7,94 | 7,9 | |||
| HEATING OPERATIONS (MODE SELECT 1-2 AUTOMATIC 3) | |||||||||||||
| ❷ | Nominal heating capacity | kW | 196,3 | 214,3 | 249,3 | 269,3 | 288,3 | 324,3 | 361,3 | 386,3 | 422,3 | ||
| ❷ | Absorbed power | kW | 60,2 | 66,1 | 75,8 | 81,9 | 87,9 | 98 | 110,5 | 118,1 | 130,3 | ||
| ❷ | C.O.P. | 3,26 | 3,24 | 3,29 | 3,29 | 3,28 | 3,31 | 3,27 | 3,27 | 3,24 | |||
| TXAETP-TXAEQP MODEL | 4200 | 4220 | 4250 | 4270 | 4290 | 5320 | 5360 | 6380 | 6430 | ||||
| ❹ | TXAETP sound pressure | dB(A) | 58 | 59 | 60 | 60 | 61 | 61 | 62 | 62 | 62 | ||
| ❹ | TXAEQP sound pressure | dB(A) | 52 | 53 | 54 | 54 | 55 | 55 | 56 | 56 | 57 | ||
| ❺ | TXAETP sound power | dB(A) | 90 | 91 | 92 | 92 | 93 | 93 | 94 | 94 | 94 | ||
| ❺ | TXAEQP sound power | dB(A) | 84 | 85 | 86 | 86 | 87 | 87 | 88 | 88 | 89 | ||
| Scroll compressors/steps | n. | 4/4 | 4/4 | 4/4 | 4/4 | 4/4 | 5/5 | 5/5 | 6/6 | 6/6 | |||
| Circuits | n. | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | |||
| Electrical supply | V-ph-Hz | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | |||
| DIMENSIONS AND WEIGHTS | 4200 | 4220 | 4250 | 4270 | 4290 | 5320 | 5360 | 6380 | 6430 | ||||
| L – Width | mm | 2730 | 2730 | 3830 | 3830 | 3830 | 4970 | 4970 | 4970 | 4970 | |||
| H – Height | mm | 2480 | 2480 | 2480 | 2480 | 2480 | 2480 | 2480 | 2480 | 2480 | |||
| P – Depth | mm | 2260 | 2260 | 2260 | 2260 | 2260 | 2260 | 2260 | 2260 | 2260 | |||
| ❻ | TXAETP weight | kg | 2370 | 2515 | 3205 | 3345 | 3490 | 4170 | 4440 | 4490 | 4780 | ||
| ❻ | TXAEQP weight | kg | 2450 | 2595 | 3310 | 3450 | 3595 | 4310 | 4580 | 4630 | 4920 | ||
| SEASONAL ENERGY PERFORMANCE | 4200 | 4220 | 4250 | 4270 | 4290 | 5320 | 5360 | 6380 | 6430 | ||||
| TXAETP MODEL SEASONAL PERFORMANCE IN HEATING MODE – Low temperature application 35°C | |||||||||||||
| ③ | Pdesignh (EN 14825) | kW | 163 | 178 | 206 | 223 | 240 | 268 | 301 | 321 | 353 | ||
| ③ | SCOP (EN 14825) | 3,93 | 3,94 | 3,97 | 3,92 | 3,92 | 3,9 | 3,89 | 3,96 | 3,91 | |||
| ④ | ηs | % | 154 | 155 | 156 | 154 | 154 | 153 | 153 | 156 | 154 | ||
| TXAEQP MODEL SEASONAL PERFORMANCE IN HEATING MODE – Low temperature application 35°C | |||||||||||||
| ③ | Pdesignh (EN 14825) | kW | 160 | 175 | 203 | 220 | 236 | 265 | 296 | 316 | 346 | ||
| ③ | SCOP (EN 14825) | 3,87 | 3,91 | 3,91 | 3,87 | 3,86 | 3,85 | 3,84 | 3,9 | 3,84 | |||
| ④ | ηs | % | 152 | 153 | 153 | 152 | 151 | 151 | 151 | 153 | 151 | ||
| TXAETP MODEL SEASONAL PERFORMANCE IN HEATING MODE – Medium temperature application 55°C | |||||||||||||
| ③ | Pdesignh (EN 14825) | kW | 162 | 176 | 201 | 217 | 233 | 260 | 291 | 313 | 343 | ||
| ③ | SCOP (EN 14825) | 3,15 | 3,18 | 3,23 | 3,22 | 3,22 | 3,19 | 3,21 | 3,24 | 3,21 | |||
| ④ | ηs | % | 123 | 124 | 126 | 126 | 126 | 125 | 125 | 127 | 126 | ||
| TXAEQP MODEL SEASONAL PERFORMANCE IN HEATING MODE – Medium temperature application 55°C | |||||||||||||
| ③ | Pdesignh (EN 14825) | kW | 160 | 174 | 199 | 214 | 229 | 258 | 286 | 309 | 336 | ||
| ③ | SCOP (EN 14825) | 3,11 | 3,15 | 3,19 | 3,18 | 3,18 | 3,14 | 3,17 | 3,19 | 3,15 | |||
| ④ | ηs | % | 121 | 123 | 124 | 124 | 124 | 123 | 124 | 124 | 123 | ||
- Data at the following conditions:
- ❶ Air: 35°C – Water: 12/7°C.
- ❷ Air: 7°C D.B. – 6°C W.B. – Water: 40/45°C.
- ❸ Evaporator output water: 7℃, nominal flow rate. Recovery output water: 45°C, nominal flow rate.
- ❹ In open field (Q = 2) at 10 m from the unit.
- ❺ Total sound power level in dB(A) based on measurements carried out in accordance with regulation UNI EN-ISO 9614.
- ❻ Weight referred to the unit without load and not accessorised.
- Performance according to EN 14511.
- T.E.R.: Total efficiency ratio
- ③ In Average climatic conditions, not Eurovent certified.
- ④ Seasonal energy efficiency: heating in Average climate (EU Regulations No.811/2013 and No.813/2013), not Eurovent certified.
Manuals
To view all the documents, log in to the reserved area
Technical notes
To view all the documents, log in to the reserved area
Documents
To view all the documents, log in to the reserved area
Images