Web code: EAS01
CHILLERS HEAT PUMPS AIR-cooled AXIAL fans

EasyPACK

THAEY 269÷2146
Cooling capacity 63,7÷139,4 kW
Heating capacity 70,3÷151,7 kW

Packaged reversible air-cooled heat pumps with axial fans.
Range with scroll hermetic compressors and R410A refrigerant.

Features

Key features


Complete and flexible range of accessories and set-ups

Multi-purpose for systems with 2 pipes+DHW (with optional RC100)

Integrated MASTER/SLAVE control


EasyPACK

Description

Construction features

• Compressor: hermetic rotary, scroll type, complete with thermal protection and casing heater.
• 3 capacity steps with high efficiency at partial loads.
• Water side heat exchanger: with stainless steel plates, complete with closed cell polyurethane foam rubber insulation and water flow differential pressure switch.
• Air side heat exchanger: featuring finned coil with copper pipes and aluminium fins depending on models/sizes.
• Fan: external rotor axial type electric fans equipped with internal thermal protection and accident protection grilles. The electric fans, based on the versions, are fitted with a proportional electronic device for continuous regulation of the rotation speed of the fans.
• Control: microprocessor electronic control with Adaptive Function Plus logic.
• Structure: load-bearing structure made of galvanised and painted steel plate with polyester powder coating.
• The unit is also complete with:
- fan and compressor circuit breaker switches;
- display of cooling circuit high and low pressure;
- Master/Slave control up to 4 units in parallel;
- clock board;
- control of Variable Primary Flow (VPF_R).

Versions

• T - High efficiency version with oversized condensing section (THAETY).
• S - Silenced version complete with compressor compartment soundproofing, reduced speed fans, and oversized condensing section (THAESY).
• Q - Super-silenced version complete with compressor technical compartment soundproofing, super-reduced speed fans and oversized condensing section (THAEQY).

Models

• THAETY: heat pump unit.
• THAESY: silenced heat pump unit.
• THAEQY: super silenced heat pump unit.

Factory fitted accessories

• Shell and tube evaporator.
• PUMP with single or double electric pump, one of which automatic in standby. The electric pumps are available in the low or high head versions.
• TANK&PUMP with 230 to 440 litre integrated buffer tank (depending on models) and single or double electric pump, complete with expansion tank, air vent valves, safety valve, and water side pressure gauge.
• Inverter pump control for unit start-up.
• Desuperheater.
• 100% heat recovery unit
• Electronic expansion valve.
• Condensing control (standard in S-Q versions).
• Condensing control with fans with EC motor.
• Condensing control with over-pressure fans (T version only)
• Power factor correction capacitors (cosφ > 0.94).
• Forced limit of power consumption.
• Forced noise limit.
• Energy parameter measuring device.
• Optimised energy efficiency.
• Soft starter.
• Technical compartment soundproofing.
• Compressor soundproof enclosures.
• Cooling circuit outlet and inlet valves.
• Refrigerant leak detector.
• Cooling circuit high and low pressure gauges.
• Double safety valves.
• Metal filters or coil protection nets.
• Coils in copper/copper or pre-painted copper/aluminium depending on the versions.
• Control of min/max power supply voltage.
• Digital input for double set-point.
• 4-20 mA analogue signal for shifting set-point.
• Evaporator antifreeze heater, electrical panel, buffer tank, electric pumps and heat exchangers for heat recovery, if applicable.
• Buffer tank integrative heaters.
• Low temperature water production.
• Interfaces for serial communication with other devices.
• Rubber anti-vibration mounts.

Separately supplied accessories

• Remote keypad with display.
• Thermostat with display.
• Rhoss supervisors for unit monitoring and remote management.
• Rhoss sequencer for integrated management of multiple chillers.

Technical data

THAETY-THAESY-THAEQY MODEL 269 279 289 296 2112 2125 2146
❷ Nominal heating capacity kW 73,4 82,4 92,4 100,5 118,5 133,1 151,7
❷ Nominal heating capacity kW 70,8 80,4 90,4 98 115 129,1 147,6
❷ Nominal heating capacity kW 70,3 77,4 88,4 95,4 111 125,5 143,6
❷ C.O.P. 3,35 3,36 3,31 3,28 3,31 3,25 3,23
❷ C.O.P. 3,32 3,36 3,31 3,29 3,3 3,27 3,27
❷ C.O.P. 3,31 3,3 3,27 3,26 3,21 3,23 3,22
❶ Nominal cooling capacity kW 67,2 76,6 86,6 93,6 107,5 121,5 139,4
❶ Nominal cooling capacity kW 66,2 74,7 85,7 89,6 104,6 119 136,9
❶ Nominal cooling capacity kW 63,7 69,7 82,7 86,6 99,1 112,1 128,5
❷ Absorbed power kW 21,91 24,52 27,92 30,64 35,8 40,95 46,97
❷ Absorbed power kW 21,33 23,93 27,31 29,79 34,85 39,48 45,14
❷ Absorbed power kW 21,24 23,45 27,03 29,26 34,58 38,85 44,6
THAEY MODEL 269 279 289 296 2112 2125 2146
❸ THAETY sound pressure dB(A) 50 51 51 51 53 54 54
❸ THAESY sound pressure dB(A) 46 47 47 47 49 50 50
❸ THAEQY sound pressure dB(A) 42 42 43 43 46 47 47
❹ THAETY sound power dB(A) 82 83 83 83 85 86 86
❹ THAESY sound power dB(A) 78 79 79 79 81 82 82
❹ THAEQY sound power dB(A) 74 74 75 75 78 79 79
Scroll compressors/steps n. 2/3 2/3 2/3 2/3 2/3 2/3 2/3
Circuits n. 1 1 1 1 1 1 1
Electrical supply V-ph-Hz 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50
DIMENSIONS AND WEIGHT 269 279 289 296 2112 2125 269
W – Width of version T – S – Q mm 3250 3250 3250 3250 3450 3450 3450
H – Height of version T – S mm 1700 1700 1700 1700 2000 2000 2000
H – Height of version Q mm 1520 1520 1520 1520 2000 2000 2000
D – Depth of version T – S – Q mm 1210 1210 1210 1210 1520 1520 1520
❺ THAETY weight kg 915 930 935 980 1240 1280 1355
SEASONAL ENERGY PERFORMANCE 269 279 289 296 2112 2125 2146
THAETY MODEL SEASONAL PERFORMANCE IN HEATING MODE
③ Pdesignh (EN 14825) kW 53 60 67 91 108 121 138
③ SCOP (EN 14825) 4,07 4,04 3,99 3,9 4,03 3,9 3,88
④ ηs % 160 159 157 153 158 153 152
④ Energy class A++ A++ A++ - - - -
THAESY MODEL SEASONAL PERFORMANCE IN HEATING MODE
③ Pdesignh (EN 14825) kW 51 58 66 89 104 117 134
③ SCOP (EN 14825) 4,06 4,08 4 3,93 4,03 3,96 3,93
④ ηs % 159 160 157 154 158 155 154
④ Energy class A++ A++ A++ - - - -
THAEQY MODEL SEASONAL PERFORMANCE IN HEATING MODE
③ Pdesignh (EN 14825) kW 51 56 65 69 100 114 130
③ SCOP (EN 14825) 4,06 4,04 3,99 3,99 3,94 3,92 3,89
④ ηs % 159 159 157 157 154 154 152
④ Energy class A++ A++ A++ A++ - - -
  • Data at the following conditions:
  • ❶ Air: 35°C – Water: 12/7°C
  • ❷ Air: 7°C, D.B. – 6°C W.B.- Water: 40/45°C.
  • ❸ In open field (Q = 2) at 10 m from the unit.
  • ❹ Total sound power level in dB(A) based on measurements carried out in accordance with regulation UNI EN-ISO 9614.
  • ❺ Weight referred to the unit without load and not accessorised.
  • ■ THAESY silenced versions.
  • ■ TCAEQY-THAEQY super-silenced versions.
  • Performance according to EN 14511.
  • ③ In Average climatic conditions, low temperature application (35°C)
  • ④ Seasonal energy efficiency: low temperature heating in Average climate (EU Regulations No.811/2013 and No.813/2013 – class between D and A+++)

Manuals

To view all the documents, log in to the reserved area

Technical notes

To view all the documents, log in to the reserved area

Documents

To view all the documents, log in to the reserved area

Images

Format: TIF
Format: tif
Request information about this product









    Find an agent or a reseller.

    Find a reseller in your area for a customized offer on Rhoss air conditioning solutions.